MS6 REDUCED VOLTAGE STARTER
Page 19
6 FAULTS
Fault (display) Description
IOC Instantaneous Over Current
- Current has reached a value of 1000% of stack size
- Usually a short circuit on the output or misfiring of SCR’s
- This fault cannot be disabled
MTR OVRLD Motor Thermal Overload (calculated)
- motor has been drawing over 100% of motor nameplate current
for a specified amount of time based on the class of overload
selected in group 15 parameter 2
- after this fault has occurred the Opal Pro will not allow a reset
for approx. 6 minutes (this is to allow the motor to cool down)
- this fault can be disabled in group 15 parameter 2
PHASE LOSS Incoming Phase Loss
- one of the incoming phases is missing or abnormally low
- phase voltages can be read in group 1 parameters 2, 3, and 4
- this fault will not be triggered until the motor is commanded to
start
- this fault cannot be disabled
SHEAR PIN Excessive Motor Current While Running
- if the Opal Pro is phased fully on and the motor is up to speed
this fault will be triggered if the current goes above 300%
- this fault can be disabled in group 15 parameter 1
SHORTED SCR Shorted SCR Fault
- this fault will not be triggered until the motor is commanded to
start
- this fault cannot be disabled
HEAT SINK OT Heat Sink Over Temperature
- One of three temperature switches mounted on the heat sink has
been triggered
- These switches trigger at approx. 85 degrees Celsius
- The switches are only mounted on units which include fans
- This fault cannot be disabled
COMM FLT Communication Fault
- a loss of communication between the Opal Pro and the master
device has been detected based on a watch dog bit that is sent
back an forth
- this fault is disabled when no communication cards are installed
on the Opal Pro
- this fault can also be disabled in group 15 parameter 3
- the time delay for the watch dog bit can be set in group 15
parameter 4
POWERING UP Power Up Sequence
- the Opal Pro will be faulted for the first 6 seconds after the
120VAC control power is applied
- this allows time for everything to initialize and then a fault reset
is automatically applied at the end of the 6 seconds