MS6 REDUCED VOLTAGE STARTER Page 9 1.2.3 MOTOR AND LOAD TYPES Squirrel Cage Motors Squirrel cage motors, with a single winding and of any NEMA design
MS6 REDUCED VOLTAGE STARTER Page 10 2 SPECIFICATIONS 2.1 POWER RATING Power 3 phase, 200-600 VAC, 50/60Hz Control 115VAC 50Hz or 120VAC 60Hz Ra
MS6 REDUCED VOLTAGE STARTER Page 11 2.4 FUSE SIZING HP J FUSE AMPS OPAL PRO MODEL MOTOR FLC 240V 460V 575V FAST ACTING TIME DELAY 20 --- 15 20
MS6 REDUCED VOLTAGE STARTER Page 12 2.5 DIMENSIONS 2.5.1 STANDARD UNIT DIMENSIONS MODEL HEIGHT WIDTH DEPTH WEIGHT MS6-30-N1 43.2cm(17”) 30.5cm(12
MS6 REDUCED VOLTAGE STARTER Page 13 3 TERMINALS CONTROL POWER INPUT 1 Control Power Line 1 (120VAC ± 10%) 2 Control Power Neutral Power for the con
MS6 REDUCED VOLTAGE STARTER Page 14 DRY CONTACT RELAY OUTPUTS 10 Fault Relay Common 11 Fault Relay N.C. 12 Fault Relay N.O. The fault relay is en
MS6 REDUCED VOLTAGE STARTER Page 15 4 KEY PAD OPERATION Actual Mode This is the mode that the unit will be in on power up. If the unit is healthy t
MS6 REDUCED VOLTAGE STARTER Page 16 5 INSTALLATION AND START-UP 5.1 INSPECTION • The Opal Pro has been packaged to protect it from damage caused by
MS6 REDUCED VOLTAGE STARTER Page 17 5.4 WIRING GUIDELINES • The electrical code requires that an approved circuit disconnecting device be installed
MS6 REDUCED VOLTAGE STARTER Page 18 5.5 START-UP 5.5.1 BEFORE POWER-UP • Ensure that all electrical connections are completed as shown on the schema
Opal Pro MS6 SERIES SOLID STATE REDUCED VOLTAGE STARTER FOR 3 PHASE INDUCTION MOTORS Revision 1.08 - 01/2011
MS6 REDUCED VOLTAGE STARTER Page 19 6 FAULTS Fault (display) Description IOC Instantaneous Over Current - Current has reached a value of 1000% of
MS6 REDUCED VOLTAGE STARTER Page 20 7 FEATURES 7.1 SOFT STOP • This provides a controlled stopping method to eliminate the water hammering effect as
MS6 REDUCED VOLTAGE STARTER Page 21 7.5 SHORTED SCR DETECTION • This option provides protection against the unlikely event of a shorted Silicon Cont
MS6 REDUCED VOLTAGE STARTER Page 22 7.7 DC INJECTION BRAKING • DC injection braking provides smooth braking for AC induction motors. • DC injection
MS6 REDUCED VOLTAGE STARTER Page 23 8 PARAMETERS GROUP PARAMETER DESCRIPTION RANGE ACCESS 1 Actual Values 101 Current of the motor in Amps
MS6 REDUCED VOLTAGE STARTER Page 24 10 Start Control 1001 Start \ Stop control - 2 wire means that you have a single maintained start contac
MS6 REDUCED VOLTAGE STARTER Page 25 1006 Jog Accelerating Current Limit - This is the current limit that will be used when in the jog mode - When
MS6 REDUCED VOLTAGE STARTER Page 26 12 Analog I/O 1201 Analog Output - This parameter designates what signal will be sent out the analog outpu
MS6 REDUCED VOLTAGE STARTER Page 27 15 Faults 1501 Shear Pin Flt - Enables and disables the shear pin fault - The shear pin fault is automa
MS6 REDUCED VOLTAGE STARTER Page 28 9 SPARES 9.1 SPARE PARTS Model SCR Current Transformer Control Card Stack ID Card MOV MS6-30 N10SP03(61A SCR)
MS6 REDUCED VOLTAGE STARTER Page 2
MS6 REDUCED VOLTAGE STARTER Page 29 10 CONNECTION DRAWINGS 10.1 TWO WIRE CONTROL Enable must be closed for starter to operate
MS6 REDUCED VOLTAGE STARTER Page 30 10.2 THREE WIRE CONTROL Enable must be closed for starter to operate
MS6 REDUCED VOLTAGE STARTER Page 31 10.3 THREE WIRE REVERSING Enable must be closed for starter to operate
MS6 REDUCED VOLTAGE STARTER Page 32 10.4 THREE WIRE WITH BY-PASS Enable must be closed for starter to operate
MS6 REDUCED VOLTAGE STARTER Page 33 10.5 THREE WIRE CONTROL WITH SHORTED SCR DETECTION Enable must be closed for starter to operate
MS6 REDUCED VOLTAGE STARTER Page 34 10.6 DCI FOR 80 AMP UNITS AND BELOW Enable must be closed for starter to operate
MS6 REDUCED VOLTAGE STARTER Page 35 10.7 DCI FOR 125 AMP UNITS AND ABOVE Enable must be closed for starter to operate
MS6 REDUCED VOLTAGE STARTER Page 36 10.8 INTEGRATED BY-PASS FOR 200A AND ABOVE CONTACTORS.- BYPASS RELAY MUST BE USEDNEUTRALFU4115VAC/50HZ120VAC/60H
www.safdrives.comemail: [email protected](Replies given within 24 hours)18 Neville Street, Unit CNew Hamburg, ON N3A 4G7Tel: 519-662-6489Fax: 1
MS6 REDUCED VOLTAGE STARTER Page 3 FOR YOUR SAFETY Only qualified personnel should install this equipment, after first reading and understandi
MS6 REDUCED VOLTAGE STARTER Page 4
MS6 REDUCED VOLTAGE STARTER Page 5 TABLE OF CONTENTS 1 MS6 GENERAL DESCRIPTION...
MS6 REDUCED VOLTAGE STARTER Page 6 7 FEATURES...
MS6 REDUCED VOLTAGE STARTER Page 7 1 MS6 GENERAL DESCRIPTION 1.1 OVERVIEW The Opal Pro series is a processor controlled line of solid state reduced v
MS6 REDUCED VOLTAGE STARTER Page 8 1.1.2 OPTIONAL FEATURES • By-Pass Contactor Once the motor has reached operational speed, the by-pass contactor i