Saf OPAL Pro MS6 User Manual Page 26

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 25
MS6 REDUCED VOLTAGE STARTER
Page 25
1006 Jog Accelerating Current Limit
- This is the current limit that will be used when in the jog
mode
- When jog is initiated the current will ramp up to this
value in 1 second and remain here for the amount of time
specified in parameter 1008.
0% - 400% Read\Write
1007 Jog Current Limit
- This is the current limit that will be used in jog mode after
the acceleration time has elapsed
0% - 400% Read\Write
1008 Jog Ramp
- This is the amount of time that the starter will regulate the
accelerating current set in parameter 1006 in jog mode
before dropping to the current limit set in parameter
1007
-a value of zero will cause the starter to go directly to
regulating the current set in parameter 1007
0 – 5 seconds Read\Write
11 Stop Control
1101 Stop Mode
- Coast means that the Opal will inhibit firing of the
SCR’s as soon as the stop command is received
- Soft Stop means that the Opal will ramp down the
current in the amount of time specified in parameter
1102
Coast
Soft Stop
DC Injection
Read\Write
1102 Sft Stop Step
- This is the amount of motor voltage that the output
will step down to when a stop is commanded. If this
value is set to high the motor will go through a state of
instability.
50% – 85% Read\Write
1103 Sft Stop Rmp
- This is the amount of time that it will take to ramp the
voltage down from the step voltage to 35% of the
motor voltage
2 – 60 seconds Read\Write
1104 DCI Current
- this is the amount of current that will be regulated during
DC Injection stopping (represented as a percentage of
nameplate current)
100% – 300% Read\Write
1105 DCI Time
- this is the amount of time that the Opal will DC inject for
1 – 60 seconds Read\Write
Page view 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 37 38

Comments to this Manuals

No comments